48V 200Ah Energy Storage LiFePo4 Battery Modular
  • 48V 200Ah Energy Storage LiFePo4 Battery Modular
  • 48V 200Ah Energy Storage LiFePo4 Battery Modular
  • 48V 200Ah Energy Storage LiFePo4 Battery Modular
  • video

48V 200Ah Energy Storage LiFePo4 Battery Modular

Brand : EnrSaver

Product origin : China

Delivery time : 7-30day

Supply capacity : 5000 Pcs/Day

● Capable of High-Powered Emergency-Backup and Off-Grid Functionality
● Highest Efficiency Thanks to a Real High-Voltage Series Connection
● The Quick Plug Connector Design Quick Wiring and Allows for Maximum Flexibility and Ease of Use
● Grand A Lithium Iron Phosphate (LFP) Battery: Maximum Safety, Life Cycle, and Power
● Compatible With Leading High Voltage Battery Inverters
● Highest Safety Standards
● The 48V LiFePO4 battery modules can be customized, also 200Ah capacity.

Download

48V 200Ah Energy Storage LiFePo4 Battery Modular

1、Scope of application documents

The specification of this product is only applicable to the protection parameters of a rechargeable lithium-ion battery Product and cell designed by Foshan EnrSaver New Energy Technology Co., Ltd.

 

2、The Specification Amendment

If the raw materials, production processing, production system or battery usage environments & other conditions need to be changed, the amendment side needs provide the written advice to the other side, only the both sides come to agreement, the amendment will be effective.

 

3、Product or Cell testing conditions

It is recommended to use newly produced battery packs and new cells for related tests.Unless specified, testing and measurement shall be done under temperature of 20±5℃ and relative humidity of 45~75%.

 

4、Standard

4.1 Reference Standard GB 31241-2014 UL1642

GB/T 31486-2015

GB/T 31485-2015

GB/T 31484-2015

4.2 Measuring Instrument and Apparatus

.1 Dimension Measuring Instrument

The dimension measurement shall be implemented by instruments with equal or more precision scale of 0.02mm.

 

.2 Voltmeter

Standard class specified in the national standard or more sensitive class having inner impedance more than 10kΩ/V

 

.3 Ammeter

Standard class specified in the national standard or more sensitive class. Total external resistance including ammeter and wire is less than 0.01Ω.

 

.4 Impedance Meter

Impedance shall be measured by a sinusoidal alternating current method(1kHz LCR meter).

 

4.3 Testing Conditions (Unless Specially Requirements) Atmosphere Pressure : 86~106kPa Temperature:20℃±5℃

Relative Humidity:≤75%



 

5. Main specifications (IFP23140160-100Ah )

 

5.1 Cell Battery specifications

 

N

o

Item

General Parameter

Remark

 

1

 

Rated Capacity

Typical

100Ah

 

Standard discharge after Standard charge

Minimum

100Ah

2

Nominal Voltage

3.2V

Mean Operation Voltage

 

3

 

Internal Impedance

 

≤0.4mΩ

Under 20±5℃ Environment Temperature , the Usage Frequency  of  Fully  Charge( 1KHz) , Use AC Internal Impedance

test machine to test

 

4

 

Standard charge

Constant Current 0.5C5A Constant Voltage 3.65V

0.02C5A cut-off

Charge time : Approx2.5h

 

5

 

Rapid Charge

Constant Current 1C5A Constant Voltage 3.65V

0.02C5A cut-off

Charge time : Approx1.5h

 

6

Standard Charge Cut-off Voltage

 

3.65V

Voltage of the battery when the Charge

is stopped

 

7

Standard Discharge Cut-off Voltage

 

2.5V

Voltage  of the battery when the discharge is stopped

8

Standard discharge

Constant current 1C5A end voltage 2.5 V

100A

9

Maximum discharge current

Constant current:1C5A end voltage:2.5 V

100A@≧0℃

 

10

 

Dimension

Thickness:48±0.5mm

 

Initial Dimension

Width:120.6±0.8mm

Height:173.9±0.8mm

11

Weight

1150g±0.05kg

APPROX

 

12

 

Operating Temperature Range

 

Temperature:-20~60℃ Humidity: ≤65%RH

Recommended charge/discharge current≤ 1I1 (50A),when cell temperature is lower than0℃, Recommended cool the cell, when cell temperature is higher than 60℃

13

Storage Temperature

Range

-20℃ ~25℃

Recommend( 25±3℃ );≤90%RH storage

moisture range.


5.1 Battery Pack specifications for single module

 

No

Item

General Parameter

Remark

1

Combination method

15S2P


2

Rated Capacity

Typical

200Ah

Standard discharge after Standard charge

package)

Minimum

196Ah

3

Factory Voltage

48V-50.5V

Mean Operation Voltage

4

Voltage at end of Discharge

<=40.5V

Discharge Cut-off Voltage

5

Charging Voltage

54.6V


 

6

 

Internal Impedance

 

≤100mΩ

Under 20±5℃ Environment Temperature , the Usage Frequency of Fully

Charge( 1KHz) , Use AC Internal Impedance

test machine to test

 

7

 

Max Charging Current(Icm)

 

100A

Ampere-meter ,Maximum allowable charging current of the battery pack

 

8

 

Limited Charging Voltage(Ucl)

 

54.6V

 

Volta-meter (Serial*3.6V) ,Battery pack safe charging voltage

9

Max Discharging current

100A

Maximum discharge current allowed by the battery pack

 

10

Discharge Cut-off voltage(Udo)

 

40.5V

Voltage of the battery when the discharge is stopped

 

11

 

Operation Temperature Range

Charge:0~55℃


Discharge: -20~60℃

 

12

 

Storage Temperature Range

 

-20℃~25℃

Recommend(25±3℃);≤90%RH storage

moisture range.

 

13

Single module Size/weight

680*442* 220mm /75Kg

1PCS of module weight: 90kg

Main control box size/weight

/

/


5.3 System composition parameters

No

Item

General Parameter

Remark

1

Combination method

PACK*2-15

Support 2 to 15 sets of battery pack to work in parallel or series

2

Rated Capacity

Typical

standard

Standard discharge after Standard charge

package)

3


Minimum

standard


4

Factory Voltage

48V-50V

Mean Operation Voltage

5

Voltage at end of Discharge

<=40.5V

Discharge Cut-off Voltage

6

Charging Voltage

54.6V

3.6V/cell

 

 

7

 

 

Internal Impedance

 

 

≤100mΩ

Internal resistance measured at AC 1KHZ after 50% charge

The measure must uses the new batteries that within one week after shipment and

cycles less than 5 times

8

Standard charge

standard

50A*number of parallel strings

9

Standard discharge

standard

100A* number of parallel strings

10

Maximum Continuous Charge Current

standard

50A* number of parallel strings

11

Maximum Continuous Discharge Current

standard

100A* number of parallel strings

12

Operation Temperature Range

Charge:0~55℃


13


Discharge: -20~60℃


 

 

14

 

 

Storage Temperature Range

 

 

-20℃~25℃

 

Recommend(25±3℃);≤90%RH storage moisture range.

15

System size

standard


16

System weight

standard


5.3.1 Battery Management System 电池管理系统规A:BMS function introduction(BMS 功能介绍) 1):The BMS is designed for 15 series lithium battery.

2):The BMS have all functions which are :(该 BMS 系统具有以下一些功能)

.1 overcharge detection function(过充电保护功能)

.2 over discharge detection function(过放电保护功能)

.3 over current detection function(过电流保护功能)

.4 short detection function(短路保护功能)

.5 Temperature detection function 温度保护功能

.6 balance function(均衡功能)

.7 communicate function (通讯功能)

.8 Alarm function (告警功能,电量板显示)

.9 Total capacity function (总容量功能)

.10 Storage history function (存储历史记录功能)

B: BMS Protect parameter(电池管理系统保护参数)(software set)

Items

Details

Standard

 

Cell overcharge protection

Overcharge detection voltage

3.65±0.025V

Overcharge detection delay time

Typical:1.0s

Overcharge release voltage

3.4±0.05V

 

 

Cell over-discharge protection

Over-discharge detection voltage

2.7±0.5V

Over-discharge detection delay time

Typical:1.0s

 

Over-discharge release voltage

3.0±0.1V

or charge

 

 

 

Over-current protection

discharge Over-current protection current1

120±10A

discharge Over-current detection delay time 1

5S

discharge Over-current protection current 2

200±10A

discharge Over-current detection delay time 2

≤600m±50ms

Charge Over-current protection current

120±10A

 

 

 

Short protection

Short protection current

300±50A

Protection condition

Load short

Detection delay time

≤30ms

Protection release condition

Charging release

 

 

 

 

 

Temperature(T) protection

Charge high T protection

55±3℃

Charge high T recover

50±5℃

Discharge high T protection

65±5℃

Discharge high T recover

55±5℃

Charge low T protection

-5±5℃

Charge low T recover

0±5℃

Discharge low T protection

-20±5℃

Discharge low T recover

-15±5℃

Balance

Balance threshold voltage

3.4V


 

 

 

Communication

It has CAN and RS485 ,RS232 standard communication interface, it real-time monitoring the capacity of battery bank, the voltage, current,environment temperature, and charging/discharging current,

RS485,RS232,Baud rate:9600Kb/S, CAN common Baud rate:500K/S,

Master address:CODE 1.slave address:2-15 ,any number

Host software:

 

Alarm

It has over-temperature, over charge, under-voltage, over-current, short

circuit alarm Function.

5. Appearance and structural dimensions 

There shall be no such defect as scratch, bur and other mechanical scratch, and the connector should be no rust dirt. The structure and dimensions see attached drawing of the product.

 

5.1 Main control box 外观

Battery module

image.png

No.

Description

Silk-screen

Remark

1

UES0600

P+ P+

Output terminal

2

UES0600

P- P-

Output terminal

3

LCD



4

LCD Key



5

Switch



6

port Reset button

RST

For reset the batter

7

LED

RUN

Operation indicator

8

LED

ALM

Alarm indicator

9

Dial switch

ADS

Set the address

10

LED

CAPACITY

Capacity indicator

11

Do



12

RS485A Port

RS485

RS485 and inverter connection port

13

CANbus Port

CANbus

CANbus and inverter connection port

14

RS232 Port

RS232

RS232 communication port

15

RS485B port

RS485

RS485 parallel communication interface


16

RS485B port

RS485

RS485 parallel communication interface

 

If there is any change in the pin position of the communication line, the customer shall be notified in writing or provided with supporting communication wire.通信线脚位如有变,需书面知会客户或提供配套通信线材.

 

 


并机通信

 

spacer.gif image.png

RS485-8P8C 立式 RJ45 插座

RS485-8P8C 立式 RJ45 插座


RJ45 引脚

定义说明

RJ45 引脚

定义说明


1

RS485-B

916

RS485-B


2

RS485-A

1015

RS485-A














对外通信

 

 image.png

RS485/CAN 立式 RJ45 插座,任选一种



RJ45 引脚

定义说明




CAN-H/RS485-B




AN-L/RS485-A


















6.1 SOC Indicator & Status Indicator Guides

Chart 1: Battery Status

 

 

 

 

 

 

 

SOC

ALARM

RUN

Chart 2: Battery Capacity

status

charge

discharge

SOC

L4

L3

L2

L1

L4

L3

L2

L1

0-25%

OFF

OFF

OFF

flash

OFF

OFF

OFF

light

25-50%

OFF

OFF

flash

light

OFF

OFF

light

light

50-75%

OFF

flash

light

light

OFF

light

light

light

>75%

flash

light

light

light

light

light

light

light

RUN LED

light

flash

Chart 3: LED flash mode

mode

light

off

Led Flash1

0.25S

3.75S

Led Flash2

0.5S

0.5S

Led Flash3

0.5S

1.5S

Chart4: LED flash mode

System status

 

Run status

RUN

ALM

SOC

 

REMARK

 

 

 

 

 

 

 

Power off

sleep

off

off

off

off

off

off

All led off

Stand by

normal

flash

off

off

off

off

off

Into stand by mode


 

 

charge

normal

light

off

Lighting for SOC

The high SOC LED flash2

Alarm OCP

light

off

Lighting for SOC

The high SOC LED flash2

OVP

Flash1


off

off

off

off


OTP,OCP

Flash1

Flash1

off

off

off

off


 

 

 

discharge

normal

Flash3

off

Lighting for SOC


Alarm

Flash3

Flash3

Lighting for SOC


 

OTP,OCP,SOP

 

off

 

light

 

off

 

off

 

off

 

off

Discharge off,BMS into deep sleep mode and it without

charge more than 48H

UVP

off

off

off

off

off

off

Discharge off

 

Address Switch function (Only in Parallel)(地址设置)

image.png

 

Complete product image 完整产品图:

image.png

 

6. Storage and Others

6.1 Long Time Storage

If stored for a long time(don’t used,exceed three months), the cell should be stored in drying and cooling place. The PACK is to be stored in a condition that the temperature of 23±2℃ and the humidity 0f 45%- 75%. Long-term use of unused batteries to recharge every 3 months。Ensure that the battery voltage is within the above range。

 

Appendix

Li-ion battery operation instructions and precautions

Preface

This document of 'Handling Precautions and Guideline Li-ion Rechargeable Batteries' shall be applied to the battery cells manufactured by EnrSaver.

Note (1) :

The customer is requested to contact Foshan EnrSaver New Energy Technology Co., Ltd.. in advance, if and when the customer needs other applications or operating conditions than those described in this document. Additional experimentation may be required to verify performance and safety under such conditions.

Note (2)

Foshan EnrSaver New Energy Technology Co., Ltd. will take no responsibility for any accident when the cell is used under other conditions than those described in this Document.

Note (3):声明三

Foshan EnrSaver New Energy Technology Co., Ltd. will inform, in a written form, the customer of improvement(s) regarding proper use and handling of the cell, if it is deemed necessary.

 

 

Warning!

— Do not immerse the battery in water or allow it to get wet.

— Do not use or store the battery near sources of heat such as a fire or heater.

— Do not use any chargers other than those recommended by TGPRO.

— Do not reverse the positive(+) and negative(-) terminals.

— Do not connect the battery directly to wall outlets or car cigarette-lighter sockets.

— Do not put the battery into a fire or apply direct heat to it.

— Do not short-circuit the battery by connecting wires or other metal objects to the positive(+) and negative(-) terminals.

— Do not pierce the battery casing with a nail or other sharp object, break it open with a hammer, or step on it.

— Do not strike, throw or subject the battery to sever physical shock.

— Do not directly solder the battery terminals.

— Do not attempt to disassemble or modify the battery in any way.

— Do not place the battery in a microwave oven or pressurized container.

— Do not use the battery in combination with primary batteries(such as dry-cell batteries) or batteries of different capacity, type or brand.

— Do not use the battery if it gives off an odor, generates heat, becomes discolored or deformed, or appears abnormal in any way. If the battery is in use or being recharged, remove it from


the device or charger immediately and discontinue use.

Caution!

Do not use or store the battery where is exposed to extremely hot, such as under window of a car in direct sunlight in a hot day. Otherwise, the battery may be overheated. This can also reduce battery performance and/or shorten service life.

 

If the battery leaks and electrolyte gets in your eyes, do not rub them. Instead, rinse them with clean running water and immediately seek medical attention. If left as is, electrolyte can cause eye injury.


Responsibility
Social welfare
Company Style
Group Photo of Factory Staff
FAQ
Do you have a certificate?
All our products have certificates, mainly European certificates, CE, TUV, DEKRA, etc....more
Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right